• Output isolation transformer
• Up to 91% efficiency
• Static by-pass
• LCD front panel
• 64 events memory
• RS232 and relay contacts
• Custom input and output voltage ranges
• SNMP compatible communication
• T-MON remote monitoring software
• Parallel operation
• 2 years warranty
• 10 years spare parts support
MODEL |
105XA |
107XA |
110 |
115 |
Power (kVA) |
5 |
7 |
10 |
15 |
INPUT |
||||
Voltage |
220/230 VAC P + N + G ± 15% |
|||
By-pass voltage |
220/230 VAC P + N ± 10% |
|||
Frequency |
50Hz / 60Hz ± 5% |
|||
OUTPUT |
||||
Power (kW) |
3,25 |
4,55 |
7 |
10,5 |
Power factor |
0.65 |
0.7 |
||
Voltage |
220/230 VAC P + N ± 1% |
|||
Frequency |
50Hz (60Hz on request) |
|||
Frequency tolerance |
Line synchronized: ± 2% , free running: ± 0,2% |
|||
Efficiency (at 100% load) |
up to 90% |
up to 91% |
||
Crest factor |
3:1 |
|||
Overload protection |
100%-125% load: 10 min., 125%-150% load: 1 min., > 150% load: by pass |
|||
Short circuit protection |
Electronic short circuit protection |
|||
Voltage THD |
< 3% |
|||
BATTERIES |
||||
Type |
Sealed Lead Acid - Maintenance Free |
|||
Number of batteries |
16 |
18 |
20 |
|
Float charging voltage |
216 VDC |
243 VDC |
270 VDC |
|
End of discharge voltage |
160 VDC |
180 VDC |
200 VDC |
|
Battery cabinet |
Internal |
External |
||
Battery ambient temperature |
25°C |
|||
Battery protection |
Automatic circuit breaker |
|||
Battery test |
Optional |
|||
GENERAL |
||||
Standards |
EN 62040-1,EN62040-2 |
|||
Serial communication |
Dry contacts & RS232 |
|||
Software |
T-Mon UPS Management Software (3 clients, +1 server management std.) |
|||
Temperature range |
0°C - 40°C |
|||
Ventilation |
Forced air cooling |
|||
Relative humidity |
< 90% (non-condensing) |
|||
Protection degree |
IP20 |
|||
Altitude |
< 2000m. |
|||
Acoustic noise |
< 45 dBA |
|||
Weight without batteries (kg) |
60 |
75 |
82 |
107 |
Dimensions (mm) HxWxD |
595x265x600 |
645x265x670 |
720x265x740 |
775x300x800 |
OPTIONS |
||||
Different input / output voltage |
Please ask |
|||
Input transformer |
Galvanic isolation transformer at the input (in external cabinet) |
|||
6kVA & 7kVA |
Previous, output PF:0.7 versions (4200W - 4900W) available on request |
|||
MBS |
Maintenance Bypass Switch for complete isolation |
|||
Adaptors |
SNMP, MODBUS, Remote Mon. Panel, RS485 |
|||
Parallel operation |
N+1 (up to 4 units) |