X
+970-2-2422931 | info@nextwave.ps

Nextwave Giga power 2 kva online


  • High frequency on-line double conversion technology.
  • DSP (Digital signal processors) control technology.
  • Active power factor correction (APFC), input power factor up to 0.99
  • Output power factor 0.9
  • Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz) .
  • Auto sensing frequency.
  • 50 / 60 Hz frequency conversion
  • Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode.
  • Cold start
  • Rear ventilation design and variable speed fan
  • Effective software and hardware protection
  • Quick and stable charging, 90% capacity restoredin 3 h (standard model UPS)
  • Linear derating in low voltage input reducing battery discharging times
  • Settable delayed start when power is restored
  • Advanced battery management (ABM)

Multi-platform communications: RS232 (standard), USB /  RS485 / SNMP


Model Nextwave Giga power 2 kva online
Cabacity 2 KVA /1800 W
INPUT  
Rated voltage 208 / 220 /230 /240 Vac
Voltage Range 110 ~ 176 Vac ( linear derating between 50% and 100% load ); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%)



          
Frequency  40 ~ 70 Hz (auto-sensing) 
Power factor  ≥ 0.99
Bypass voltage range  - 25% ~ +15% (settable)
Total harmonic distortion (THDi)  ≤ 6%
OUTPUT  
Voltage 208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation  ±1% 
Frequency  45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz±0.1 Hz (battery mode)
Waveform  Sinusoidal
Power factor  0.9
Total harmonic distortion (THDv) ≤ 2% (linear load), ≤ 5% (non-linear load)
Crest factor  3:1
Overload  105% ~ 125% for 1 min, 125%  ~ 150% for 30 sec  >150% for 300 ms
BATTERIES  
DC voltage  48 V (S)  
Inbuilt battery 4×9 Ah  
Charging current (max.) 1A
Recharge time Standard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery
SYSTEM  
Efficiency ≥ 92% (Mains mode)
≥ 87% (Battery mode)
≥ 97% (ECO mode)
Transfer time  Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 4 ms (typical) 
Protections  Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection 
Communications  RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) 
Display LCD + LED 
Standards  EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11,
IEC 61000-2-2, IEC 62040-2, IEC 62040-1, IEC 62040-3 
OTHERS  
Operating temperature 0℃ ~ 40℃
Storage temperature -25℃ ~ 55℃ (without batteries)
Relative Humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m ≤ 50 dB 
Dimensions (W×D×H) (mm) 191×418X335
Net weight (kg) 32
Gross weight (kg)  34