  • Advanced DSP and 3-level technology
  • Output power factor 1.0
  • Active power factor correction (APFC),
  • High efficiency 95% (up to 98% in ECO mode)
  • Advanced digital parallel technology
  • Wide input voltage range (110 ~ 288 Vac) and frequency range (40 ~ 70 Hz)
  • 50 / 60 Hz frequency auto sensing

Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output

  • Dual-input design, supporting independent bypass
  • Flexible battery configuration (settable 16 - 20 pcs batteries)
  • Digitally controlled charger
  • High charging current available (Max. 12 A)
  • Charging voltage and current configured by demands.
  • Linear derating in low voltage input reducing battery discharging times, extending the service life of battery
  • Intelligent battery management, automatic floating /equalizing charge control, charger dormancy control, increasing battery life by 50%
  • Ability to switch on the UPS with batteries
  • Settable delayed start time when mains power is restored, reducing the impact on power grid or generator
  • Fan speed varies intelligently with temperature, reducing noise and extending its service life
  • Equipped with self-aging function
  • Compact internal layout, miniaturized the complete unit for small footprint
  • LCD+LED display, multi-functional keys operation, friendly human-machine interface)
  • Powerful background software for parameters configuration
  • Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces.
  • Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check

 

 

 

 


Model Nextwave Giga power 10 kva online 3/1
Cabacity 10 KVA / 10  kw
INPUT  
Input wiring Three-phase five-wire (3Φ + N + PE)
Rated voltage 380 / 400 / 415 Vac
Voltage Range 190 ~ 305 Vac (linear derating between 50% and 100% load); 305 ~ 499 Vac (no derating)
Rated frequency  50 / 60 Hz (auto-sensing)
Frequency range 40 ~ 70 Hz
Power factor  ≥ 0.99
Bypass voltage range  - 40% ~ +15% (settable)
Total harmonic distortion (THDi)  ≤ 5%
OUTPUT  
Output wiring Single-phase three-wire (1Φ + N + PE)
Rated voltage 208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation  ±1% 
Frequency  Synchronized to bypass in mains mode; 50 / 60 Hz±0.1% Hz in battery mode
Waveform  Sinusoidal
Power factor  1
Total harmonic distortion (THDv) ≤ 1% (linear load);  ≤ 3% (non-linear load)
Crest factor  3:1
Overload  102% ~ 110% for 10 min, 110% ~ 125% for 1 min, 125% ~ 150% for 30 s
BATTERIES  
DC voltage  192 Vdc (192 ~ 240 Vdc settable)
Number of battery 16 pcs (16 ~ 20 settable)
Inbuilt battery (standard model) 16 pcs 12v9ah
Charging current Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 12 A (optional)
Recharge time Standard model: 90% capacity restored in 8 hours;  Long time model: depend on the capacity of battery
SYSTEM  
Efficiency ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode
Transfer time  0 ms
Protections  Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Communications  RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) 
Max. number of parallel connections  4
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display LCD + LED 
OTHERS  
Operating temperature 0℃ ~ 40℃
Storage temperature -25℃ ~ 55℃ (without batteries)
Relative Humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m ≤ 58 dB
Dimensions (W×D×H) (mm) 191 × 495 × 515 (H)
Net weight (kg) 26.5 (H)
Gross weight (kg)  28 (H)