X
+970-2-2422931 | info@nextwave.ps

Tescom MTR(10-90KVA)


Rack modular design
Modular design, compatible with 19” standard rack
cabinet, convenient to be integrated with servers

High power density
10/15kVA (10/15kW) power module in 2U height, saving great amount of space, easy for capacity expansion

Integrated solution for data center
UPS can be integrated with battery cabinet, PDU and external maintenance bypass, offering excellent choice for data center

Intelligent charging management
The system intelligently control the whole process of the charging and discharging, effectively improving the life time of the battery

Flexible configuration
The system can be configured to 3/3, 3/1 and 1/1 without derating

Friendly interface
7” touch color LCD with graphic display, more information displayed and easier for customer to operate

Smart sleep function
System can intelligently shutdown some power modules to increase total load rate, achieving higher efficiency

Self-aging mode
Energy internal circle technology, system can run with full load ,saving more than 90% energy


MODEL

MTR-020/10X

*MTR-030/10X

MTR-040/10X

MTR-060/10X

MTR-030/15X

*MTR-045/15X

MTR-090/15X

Capacity

20kVA/20kW

30kVA/30kW

40kVA/40kW

60kVA/60kW

30kVA/30kW

45kVA/45kW

90kVA/90kW

Power module type

PM10X (10kVA/10kW)

PM15X (15kVA/15kW)

INPUT

Phase

(1/1P - 3/1P - 3/3P) 3P+ N + G (380/400/415V)  ~  1P + N + G ( 220/230/240V)

3P+ N +G (380/400/415V) 

Voltage range

304-478Vac (line-line),100% load; 

228-304Vac load derated from 100% - %75 linearly

Frequency range

40Hz-70Hz

Power factor

> 0.99

THDi

** THDi < 4% @ 100% linear load

OUTPUT

Voltage

(1/1P - 3/1P - 3/3P) 3P+ N + G (380/400/415V)  ~  1P + N + G ( 220/230/240V)

3P+ N +G (380/400/415V) 

Voltage regulation

1.5%

Power factor

1

THDu

THD < 1% (linear load ),THD < 5.5% (non-linear load)

Crest factor

3:1

Overload capacity

110% for 1 hour; 125% for 10 min; 150% for 1 min ; 150% for 200 ms

BATTERY

Voltage

± 240 VDC for 40 batteries (selectable battery number 36-44)

Charge power

20%* System power

Charge voltage precision

±1%

SYSTEM

System efficiency

Normal mode: 95%; ECO mode: 98%; Battery mode: 94.5%

Display

7.0” Color touch screen LCD + LED + Keyboard

IP Class

IP20

Interface

Standart: RS232, RS485, dry contacts

Optional:  Expansion dry contact card

Operation / Storage temperature

0-40℃/-25-70℃

Relative humidity

0-95% (non-condensing)

Noise level

56dB (1 meter away)

58dBA (1 meter away)

Options

Parallel operation, Battery compansated battery charging, Movable cabinet with castors

PHYSICAL 

Weight (kg)

Cabinet

42

55

51

85

42

55

85

Power module

15.Mar

15.May

Dimension (mm) HxWxD

Cabinet

398x485x697

575x485x751

575x485x697

1033x485x751

398x485x697

575x485x751

1033x485x751

Height

7U

11U

11U

21U

7U

11U

21U

Power module

(2U) 85x436x590

(*) Parallel operation

(**) Only for 3/3 phase


Sales Ticket Form