• Low input current distortion - less than 3%
• High input power factor 0.99
• Power walk-in function to achieve progressive rectifier start-up
• Delayed start-up on mains power supply return
The DS 3 LEVEL Battery Care System optimises battery performance, to help extend their working life and ensure that the UPS can deliver its full-rated back-up time when called upon in an emergency.
Battery recharge: DS 3 LEVEL is designed to work with VRLA AGM and GEL lead-acid batteries including open-vented types, in addition to Ni-Cads. Specific management features include:
• One-level recharge to meet the requirements of the most common VRLA AGM batteries
• Two voltage level recharge meeting the IU characteristic
• Restricted charging to reduce electrolyte consumption and extend the life of VRLA batteries
Temperature compensation: to avoid excessive voltage being applied to the batteries in a high ambient
Battery test: to detect performance degradation and predict battery failure.
Deep discharge protection: to prevent the batteries being discharged below a level from which they cannot be recovered (especially when discharged over long periods with very low loads).
Low AC ripple current: from a high-frequency battery charger, to ensure the batteries are not subjected to this damaging element commonly experienced with some other UPS and power supply designs.
Wide input voltage range: from a rectifier that can work down to less than 40% of its nominal supply rating (at half load), removing the need to discharge the batteries
DS 3 LEVEL can be used for a wide range of applications, thanks to its configuration options, flexibility, accessories and performance levels:
• Suitable for powering capacitive loads, for example Blade servers - without any reduction in active power, from 0.9 leading to 0.9 lagging
• Modes of operation include: On-Line, Eco, Smart-Active and Stand-By/Off
• Frequency conversion mode
• Power Share connections for priority-based load shedding when the mains power supply has failed
• Cold-start facility to switch the UPS on even without a mains power supply present
• Extensive back-up time options using battery extension cabinets
• Optional battery cabinet temperature sensor to assist the temperature compensating charger
• Optional battery chargers to optimize recharge times
• Optional dual input supplies
• Optional isolation transformers for Galvanic isolation and neutral connectivity
The DS 3 LEVEL design provides exceptional performance and efficiency levels, within a very compact footprint and overall case design:
• Lowest footprint in its category - 0.26m² for the 20kVA DS 3 LEVEL with internal batteries.
• High efficiency up to 94% - saving up to 35% in dissipated energy in one year compared to a more traditional UPS (91%) resulting in a faster payback period of four years.
• High output power factor which at 0.9pF provides up to 15% more active power compared to a more traditionally sized UPS - providing greater system expansion margin for further load increases.
MODEL |
DS3L 10 |
DS3L 12 |
DS3L 15 |
DS3L 20 |
DS3L 30 |
DS3L 40 |
DS3L 60 |
DS3L 80 |
DS3L 100 |
DS3L 120 |
DS3L 160 |
DS3L 200 |
INPUT |
||||||||||||
Voltage |
380/400/415 VAC 3 Phase + N |
|||||||||||
Frequency |
50Hz. / 60Hz. |
|||||||||||
Frequency range |
40 - 72Hz. |
|||||||||||
Power factor |
0.99 |
1 |
||||||||||
Harmonic current distortion |
THDI ≤ 3% |
|||||||||||
BY PASS |
||||||||||||
Voltage |
380/400/415 VAC 3 Phase + N |
|||||||||||
Number of phases |
3 + N |
|||||||||||
Voltage range |
180 - 264 V (selectable) |
|||||||||||
Frequency |
50Hz. or 60Hz. (selectable) |
|||||||||||
Frequency tolerance |
± %5 (selectable) |
|||||||||||
OUTPUT |
||||||||||||
Power (kVA) |
10 |
12 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
160 |
200 |
Power (kW) |
9 |
10.8 |
13.5 |
18 |
27 |
36 |
54 |
72 |
90 |
108 |
160 |
200 |
Power factor |
0.9 |
1 |
||||||||||
Number of phases |
3 + N |
|||||||||||
Voltage (V) |
380 - 400 - 415 VAC (selectable) |
|||||||||||
Static Variation |
± % 1 |
|||||||||||
Dynamic Variation |
± % 3 |
|||||||||||
Crest factor |
3:1 |
|||||||||||
Voltage distortion |
≤ % 1 Linear load, ≤ % 3 Non-linear load |
|||||||||||
Frequency |
50Hz. / 60Hz. |
|||||||||||
Frequency stability during battery operation |
% 0.01 |
|||||||||||
Overload protections (0.8 PF) |
up to 115% for Continuous, 115%-125% for 10 min, 125%-150% for 1 min, 150%-168% for 5 sec |
|||||||||||
BATTERIES |
||||||||||||
Type |
VRLA AGM / GEL |
|||||||||||
Recharge time |
6 hours |
|||||||||||
INSTALLATION |
||||||||||||
Weight without batteries |
105 |
110 |
115 |
115 |
135 |
145 |
190 |
200 |
370 |
380 |
450 |
460 |
Dimensions (mm) HxWxD |
1320x440x850 |
1320x440x850 |
1600x500x850 |
1900x750x855 |
1900x850x1050 |
|||||||
Communication |
3 sockets for Communication interface/RS232/USB |
|||||||||||
Temperature range |
0ºC / +40ºC |
|||||||||||
Humidity |
%90 non-condensed |
|||||||||||
Colour |
Dark grey RAL 7016 |
|||||||||||
Acoustic noise (1m) |
< 52 dBA |
< 48 dBA |
< 52 dBA |
< 65 dBA |
< 50 dBA |
|||||||
Protection degree |
IP20 |
|||||||||||
Efficiency |
up to % 99 |
|||||||||||
Standards |
Directive EMC 2004 / 108 / CE Electromagnetic Compability Directive |
|||||||||||
Standards : Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2 |
||||||||||||
in accordance with IEC EN 62040-3 ( Voltage and Frequency Independent) VFI-SS-111 |