X
+970-2-2422931 | info@nextwave.ps

DS|POWER 110(5-80KVA)

DSP UPS are three phase in/three phase out, IGBT rectifier, Intelligent Power Module technology based, high input power factor,low THDI and DSP controlled.


• Transformerless UPS topology
• Low input current total harmonic distortion (THD)
• High input power factor
• High efficiency up to 94%
• Cold start function
• Static and maintenance by-pass switch
• Output short circuit and overload protection
• External REPO switch input
• 192 events memory (192 events 4500 alarms)
• Clock and calender (battery supported)
• Automatic battery test, remaining battery time indicator
• Temperature compansiated charge system
• Regenerative backfeed function
• 2 RS232 serial ports and 12 dry contact outputs
• 3 DSP controlled modular structure
• Optional SNMP and MODBUS adaptors
• Optional Graphical and touch panel
• 2 years warranty
• 10 years spare parts support
• Manufactured according to EC Directive; EN62040


MODEL

DS305
110

DS310
110

DS315
110

DS320
110

DS330
110

DS340
110

DS350
110

DS360
110

DS380
110

Power (kVA)

5

10

15

20

30

40

50

60

80

INPUT

Voltage

200/208 VAC three-phase + N, ± 20% (220VAC +15% -25%)

Frequency

50Hz or 60Hz selectable, ± 5Hz

Power factor

> 0,99

Harmonic current distortion

≤ 4% *

Protection

fuses, voltage tolerance, frequency tolerance, input power limit

By-pass voltage

200/208/220 VAC three-phase + N, ± 10%

By-pass protection

short circuit, voltage tolerance, frequency tolerance, VAT transfer

OUTPUT

Power factor

0,9

Voltage

200/208/220 VAC three-phase + N,  ± 1%

Frequency

50Hz or 60Hz (selectable)

Frequency tolerance

line synchronized: ± 2% / Free running: ± 0,1% (adjustable)

Efficiency

up to 94%

Crest factor

3:1

Overload protection

100-125% for 10min, 125-150% for 1min, >150% load: by-pass

Other protections

Advanced short circuit, voltage tolerance, DC balance, regenerative load, current limiting

THD (at 100% linear load)

< 3%

BATTERIES

Type

VRLA AGM / GEL / NiCd

Nominal voltage

± 192 VDC

Float / End of disch. voltage

± 216VDC  /  ± 160VDC

Battery housing

Internal

Battery cabinet

Battery ambient temp. °C 

25 °C

Protections

3 level alarm, battery fuses, charging current limit, temperature compensation(opt.)

Automatic testing

Standard every 72 hours(adjustable)

GENERAL

Standards

EMC(2004/108/EC) / LVD(2006/95/EC) - EN62040-1, EN62040-2, EN60950

User interface

4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, graphical touch-panel (opt.)

Indicators

P-N voltage, P-P voltage,Current, Power, Crest factor, Frequency ,PF, Service time

Advanced

Self diagnostics, 4 maintenance time indicators, Calibration over RS232

Communication

2 x RS232 serial ports, 4 standard and 8 optional DRY contact alarm relays

Inputs

EPO input, Interactive battery panel input, Genset input

Genset kit 

Standard (programmable)

Software

Standard T-Mon UPS Management Software (3 clients + 1 server management)

Alarm logging

Standard; with time & date 192 events, (optional 512 events)

Protections

Power module over-temperature, Over current, Temperature high alarm

Temperature range

0 °C - 40 °C

Protection degree

IP20 (other, on request)

Humidity / Altitude

90% max (noncondensed) / <1000m above sea level

Acoustic noise

≤ 57 dBA

≤ 62 dBA

≤ 64 dBA

≤ 68 dBA

Weight (kg.)

87

91

100

173

180

194

216

258

Dimensions (mm) HxWxD

1035x400x810

1440x515x850

OPTIONS

Input / Output voltage

Other special input/output voltages

Transformer

Galvanic isolation transformer at the input & output

Software

T-Mon Admin Multi UPS monitoring, T-Mon Server 50-100-200 clients, DLOG log loader

Comm. adaptors

SNMP, MODBUS, RS485, Remote Panel

Parralel operation

Up to 8 UPS

 

(*) Depending on power and input/output conditions.


Sales Ticket Form