Tescom 300 series are, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.
• Output isolation transformer
• Up to 91% efficiency
• Static by-pass
• LCD front panel
• 128 events alarm memory (4000 alarms)
• RS232 and relay contacts
• Custom input and output voltage ranges
• SNMP compatible communication
• T-MON remote monitoring software
• Parralel operation up to 4 devices
• High performance at nonlinear loads
• Custom input voltage and frequency ranges
• 2 years warranty
• 10 years spare parts support
• Manufactured according to EC Directive; EN62040
MODEL |
310 |
315 |
320 |
330 |
340 |
360 |
380 |
Power (kVA) |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
INPUT |
|||||||
Voltage |
380/400 VAC 3P + N + G ± 15% |
||||||
By-pass voltage |
380/400 VAC 3P + N ± 10% |
||||||
Input frequency |
50Hz (60Hz on request) ± 5% |
||||||
OUTPUT |
|||||||
Power (kW) |
8 |
12 |
16 |
24 |
32 |
48 |
64 |
Power factor |
0,8 |
||||||
Voltage |
380/400 VAC 3P + N |
||||||
Voltage stability |
Balanced load: ± 1%, Unbalanced load: ± 2%, Step load: ± 5% |
||||||
Voltage recovery time |
After step load: max. 25ms |
||||||
Frequency |
50Hz (60Hz on request) |
||||||
Frequency tolerance |
Line synchronized: ± 2% , free running: ± 0,2% |
||||||
Efficiency (at 100% load) |
89-91% |
90-92% |
|||||
Crest factor |
3:1 |
||||||
Overload protection |
100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass |
||||||
Short circuit protection |
Electronic short circuit protection |
||||||
Voltage THD |
Linear load: < 3% |
||||||
Non linear load: < 5% |
|||||||
BATTERIES |
|||||||
Type |
Sealed Lead Acid - Maintenance Free |
||||||
Number of batteries |
30 |
||||||
Float charging voltage |
405 VDC |
||||||
End of discharge voltage |
300 VDC |
||||||
Battery ambient temperature |
25ºC |
||||||
Battery protection |
Automatic circuit breaker |
||||||
Battery test |
Automatic every 72 hours |
||||||
GENERAL |
|||||||
Standards |
EN 62040-1,EN62040-2 |
||||||
Serial communication |
Dry contacts & RS232 |
||||||
Software |
T-Mon UPS Management Software (3 clients, +1 server management std.) |
||||||
Temperature range |
0°C - 40°C |
||||||
Ventilation |
Forced air cooling |
||||||
Relative humidity |
< 90% (non-condensing) |
||||||
Protection degree |
IP20 |
||||||
Altitude |
< 2000m above sea level |
||||||
Acoustic noise |
< 56 dBA |
< 60 dBA |
|||||
Weight without batteries (kg) |
220 |
260 |
284 |
305 |
404 |
496 |
580 |
Dimensions (mm) HxWxD |
1150x505x655 |
1390x575x820 |
1450x720x820 |
||||
OPTIONS |
|||||||
Different input / output voltage |
Please ask |
||||||
Input transformer |
Galvanic isolation transformer at the input (in external cabinet) |
||||||
Input THD |
10% (with 12 pulse or 18 pulse rectifier, according to UPS range) |
||||||
%5 (with 18 pulse rectifier, + filter), up to 100kVA |
|||||||
Input power factor |
0.95 - 0.98 (with 18 pulse rectifier) |
||||||
Adaptors |
SNMP, MODBUS, Remote Mon. Panel, RS485 |
||||||
Parallel operation |
N+1 (up to 4 units) |
||||||
(*): |
In 18Pulse & 12Pulse applications, the standard chassis dimensions may change. |