Tescom 300 series are, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.
• Output isolation transformer
• Up to 91% efficiency
• Static by-pass
• LCD front panel
• 128 events alarm memory (4000 alarms)
• RS232 and relay contacts
• Custom input and output voltage ranges
• SNMP compatible communication
• T-MON remote monitoring software
• Parralel operation up to 4 devices
• High performance at nonlinear loads
• Custom input voltage and frequency ranges
• 2 years warranty
• 10 years spare parts support
• Manufactured according to EC Directive; EN62040
MODEL |
3100 |
3120 |
3160 |
3200 |
3250 |
3300 |
Power (kVA) |
100 |
120 |
160 |
200 |
250 |
300 |
INPUT |
||||||
Voltage |
380/400 VAC 3P + N + G ± 15% |
|||||
By-pass voltage |
380/400 VAC 3P + N ± 10% |
|||||
Input frequency |
50Hz (60Hz on request) ± 5% |
|||||
OUTPUT |
||||||
Power (kW) |
80 |
96 |
128 |
160 |
200 |
240 |
Power factor |
0,8 |
|||||
Voltage |
380/400 VAC 3P + N |
|||||
Voltage stability |
Balanced load: ± 1%, Unbalanced load: ± 2%, Step load: ± 5% |
|||||
Voltage recovery time |
After step load: max. 25ms |
|||||
Frequency |
50Hz (60Hz on request) |
|||||
Frequency tolerance |
Line synchronized: ± 2% , free running: ± 0,2% |
|||||
Efficiency (at 100% load) |
90-92% |
|||||
Crest factor |
3:1 |
|||||
Overload protection |
100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass |
|||||
Short circuit protection |
Electronic short circuit protection |
|||||
Voltage THD |
Linear load: < 3% |
|||||
Non linear load: < 5% |
||||||
BATTERIES |
||||||
Type |
Sealed Lead Acid - Maintenance Free |
|||||
Number of batteries |
30 |
32 |
||||
Float charging voltage |
405 VDC |
432 VDC |
||||
End of discharge voltage |
300 VDC |
320 VDC |
||||
Battery ambient temperature |
25ºC |
|||||
Battery protection |
Automatic circuit breaker |
|||||
Battery test |
Automatic every 72 hours |
|||||
GENERAL |
||||||
Standards |
EN 62040-1,EN62040-2 |
|||||
Serial communication |
Dry contacts & RS232 |
|||||
Software |
T-Mon UPS Management Software (3 clients, +1 server management std.) |
|||||
Temperature range |
0ºC - 40ºC |
|||||
Ventilation |
Forced air cooling |
|||||
Relative humidity |
< %90 (non-condensing) |
|||||
Protection degree |
IP20 |
|||||
Altitude |
< 2000m above sea level |
|||||
Acoustic noise |
65 dBA |
70 dBA |
||||
Weight without batteries (kg) |
750 |
765 |
802 |
970 |
1328 |
1370 |
Dimensions (mm) HxWxD |
1650x1110x810 |
1730x1195x870 |
1880x1565x925 |
|||
OPTIONS |
||||||
Different input / output voltage |
Please ask |
|||||
Input transformer |
Galvanic isolation transformer at the input (in external cabinet) |
|||||
Input THD |
10% (with 12 Pulse or 18 Pulse rectifier, according to UPS range) |
|||||
5% (with 18 Pulse rectifier, + filter), up to 100kVA |
||||||
Input power factor |
0,95 - 0,98 (with 18 Pulse rectifier) |
|||||
Adaptors |
SNMP, MODBUS, Remote Mon. Panel, RS485 |
|||||
Parallel operation |
N + 1 (up to 4 units) |
|||||
(*): |
In 18Pulse & 12Pulse applications, the standard chassis dimensions may change. |