X
+970-2-2422931 | info@nextwave.ps

Nextwave GigaPower 20 kva 3/1 (20KW)


● Advanced DSP and 3-level technology

● Output power factor 1.0

● Active power factor correction (APFC), input power factor up to 0.99

● High efficiency 95% (up to 98% in ECO mode)

● Advanced digital parallel technology

●  3:1 to 1:1 model settable

● Wide input voltage range (190 ~ 499 Vac) and frequency range (40 ~ 70 Hz)

● 50 / 60 Hz frequency auto sensing

● Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output

● Dual-input design, supporting independent bypass

● Flexible battery configuration (settable 16 - 20 pcs batteries)

● Digitally controlled charger

● High charging current available (Max. 10 A)

● Charging voltage and current configured by demands

● Linear derating in low voltage input reducing battery discharging times, extending the service life of battery

● Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%

● Ability to switch on the UPS with batteries

● Settable delayed start time when mains power is restored, reducing the impact on power grid or generator

● Fan speed varies intelligently with temperature, reducing noise and extending its service life

● Equipped with self-aging function

● Compact internal layout, miniaturized the complete unit for small footprint

● LCD+LED display, multi-functional keys operation, friendly human-machine interface

● Powerful background software for parameters configuration

● Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces

● Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check

Available Options

● RS232 and smart card slot included

● Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms


Model Nextwave Giga power 20 kva online 3/1
Cabacity 20 KVA / 20 kw
INPUT  
Input wiring Three-phase five-wire (3Φ + N + PE)
Rated voltage 380 / 400 / 415 Vac
Voltage Range 190 ~ 305 Vac (linear derating between 50% and 100% load); 305 ~ 499 Vac (no derating)
Rated frequency  50 / 60 Hz (auto-sensing)
Frequency range 40 ~ 70 Hz
Power factor  ≥ 0.99
Bypass voltage range  - 40% ~ +15% (settable)
Total harmonic distortion (THDi)  ≤ 5%
OUTPUT  
Output wiring Single-phase three-wire (1Φ + N + PE)
Rated voltage 208 (PF=0.9) / 220 / 230 / 240 Vac
Voltage regulation  ±1% 
Frequency  Synchronized to bypass in mains mode; 50 / 60 Hz±0.1% Hz in battery mode
Waveform  Sinusoidal
Power factor  1
Total harmonic distortion (THDv) ≤ 1% (linear load);  ≤ 3% (non-linear load)
Crest factor  3:1
Overload  102% ~ 110% for 10 min, 110% ~ 125% for 1 min, 125% ~ 150% for 30 s
BATTERIES  
DC voltage  192 Vdc (192 ~ 240 Vdc settable)
Number of battery 16 pcs (16 ~ 20 settable)
Inbuilt battery (standard model) External 
Charging current Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 12 A (optional)
Recharge time Standard model: 90% capacity restored in 8 hours;  Long time model: depend on the capacity of battery
SYSTEM  
Efficiency ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode
Transfer time  0 ms
Protections  Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure
Communications  RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) 
Max. number of parallel connections  4
Communications RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional)
Display LCD + LED 
OTHERS  
Operating temperature 0℃ ~ 40℃
Storage temperature -25℃ ~ 55℃ (without batteries)
Relative Humidity 0 ~ 95% (non-condensing)
Altitude ≤ 1000 m, derating 1% for each additional 100 m
IP rating IP 20
Noise level at 1m ≤ 58 dB
Dimensions (W×D×H) (mm) 191 × 495 × 515 (H)
Net weight (kg) 26.5 (H)
Gross weight (kg)  28 (H)

Sales Ticket Form