● Advanced DSP and 3-level technology
● Output power factor 1.0
● Active power factor correction (APFC), input power factor up to 0.99
● High efficiency 95% (up to 98% in ECO mode)
● Advanced digital parallel technology
● 3:1 to 1:1 model settable
● Wide input voltage range (190 ~ 499 Vac) and frequency range (40 ~ 70 Hz)
● 50 / 60 Hz frequency auto sensing
● Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output
● Dual-input design, supporting independent bypass
● Flexible battery configuration (settable 16 - 20 pcs batteries)
● Digitally controlled charger
● High charging current available (Max. 10 A)
● Charging voltage and current configured by demands
● Linear derating in low voltage input reducing battery discharging times, extending the service life of battery
● Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%
● Ability to switch on the UPS with batteries
● Settable delayed start time when mains power is restored, reducing the impact on power grid or generator
● Fan speed varies intelligently with temperature, reducing noise and extending its service life
● Equipped with self-aging function
● Compact internal layout, miniaturized the complete unit for small footprint
● LCD+LED display, multi-functional keys operation, friendly human-machine interface
● Powerful background software for parameters configuration
● Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces
● Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check
Available Options
● RS232 and smart card slot included
● Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms
Model | Nextwave Giga power 20 kva online 3/1 |
Cabacity | 20 KVA / 20 kw |
INPUT | |
Input wiring | Three-phase five-wire (3Φ + N + PE) |
Rated voltage | 380 / 400 / 415 Vac |
Voltage Range | 190 ~ 305 Vac (linear derating between 50% and 100% load); 305 ~ 499 Vac (no derating) |
Rated frequency | 50 / 60 Hz (auto-sensing) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | - 40% ~ +15% (settable) |
Total harmonic distortion (THDi) | ≤ 5% |
OUTPUT | |
Output wiring | Single-phase three-wire (1Φ + N + PE) |
Rated voltage | 208 (PF=0.9) / 220 / 230 / 240 Vac |
Voltage regulation | ±1% |
Frequency | Synchronized to bypass in mains mode; 50 / 60 Hz±0.1% Hz in battery mode |
Waveform | Sinusoidal |
Power factor | 1 |
Total harmonic distortion (THDv) | ≤ 1% (linear load); ≤ 3% (non-linear load) |
Crest factor | 3:1 |
Overload | 102% ~ 110% for 10 min, 110% ~ 125% for 1 min, 125% ~ 150% for 30 s |
BATTERIES | |
DC voltage | 192 Vdc (192 ~ 240 Vdc settable) |
Number of battery | 16 pcs (16 ~ 20 settable) |
Inbuilt battery (standard model) | External |
Charging current | Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 12 A (optional) |
Recharge time | Standard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery |
SYSTEM | |
Efficiency | ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode |
Transfer time | 0 ms |
Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) |
Max. number of parallel connections | 4 |
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional) |
Display | LCD + LED |
OTHERS | |
Operating temperature | 0℃ ~ 40℃ |
Storage temperature | -25℃ ~ 55℃ (without batteries) |
Relative Humidity | 0 ~ 95% (non-condensing) |
Altitude | ≤ 1000 m, derating 1% for each additional 100 m |
IP rating | IP 20 |
Noise level at 1m | ≤ 58 dB |
Dimensions (W×D×H) (mm) | 191 × 495 × 515 (H) |
Net weight (kg) | 26.5 (H) |
Gross weight (kg) | 28 (H) |