● DSP digital control technology
● Active power factor correction (APFC), input power factor up to 0.99
● Output power factor 0.9
● Cold start
● Dual input
● Wide input voltage range (190 V ~ 485 V)
● Auto sensing frequency
● 50 / 60 Hz frequency conversion mode
● Work efficiency up to 98% in ECO mode
● Auto control fan speed when loads varies
● Auto power ON/OFF according to the load capacity set by users
● Flexible battery configuration for using 14/16/18/20 pcs batteries
● Compact internal layout, miniaturized the complete unit for small footprint
● LCD+LED display, multi-functional keys operation, friendly human-machine interface
● Powerful background software for parameters configuration and online updating
● Doubling the battery charging speed, 90% capacity restored in 4 hours (standard model UPS
● Linear derating in low voltage input, reducing battery discharging times, extending the service life of battery
● Advanced battery management (ABM), automatic floating / equalizing charge control, charger dormancy control
● Configurable switching time from battery mode to mains mode when mains power is restored, reducing the impact on power grid or generator
● Effective software and hardware protection function, powerful self-diagnostic function, abundant historical records
● Standard emergency power off (EPO)
● Standard maintenance bypass
● Standard RS232/USB communication port
● Optional RS485 / SNMP / AS400 communication port and SMS alarms
● Optional N+X redundancy parallel up to 6 units
● Optional battery temperature compensation, EMD environmental sensors
Model | Nextwave Giga power 10kva online 3/3 |
Cabacity | 10 KVA / 9 kw |
INPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac |
Voltage Range | 277 ~ 485 Vac (no derating); 190 ~ 277 Vac (linear derating between 50% and 100% load) |
Rated frequency | 50 / 60 Hz (auto-sensing) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99 |
Bypass voltage range | - 40% ~ +15% (settable) |
Total harmonic distortion (THDi) | ≤ 5% |
OUTPUT | |
Rated voltage | 360 / 380 / 400 / 415 Vac (settable) |
Voltage regulation | ±1% |
Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) |
Waveform | Sinusoidal |
Power factor | 0.9 |
Total harmonic distortion (THDv) | ≤ 2% (linear load), ≤ 5% (non-linear load) |
Crest factor | 3:1 |
Overload (Inverter) | 102% ~ 125% for 10 min, 125% ~ 150% for 1 min, > 150% for 0.5 s |
Overload | 102% ~ 125% for 20 min, 125% ~ 150% for 2 min, > 150% for 1 s |
BATTERIES | |
DC voltage | Standard model: 240 Vdc; Long time model: 192 Vdc (168 / 192 / 216 / 240V optional) |
Inbuilt battery (standard model) | 20 × 7 Ah |
Charging current | Long time model: 7 A supplied (additional 7 A is optional) Standard model: 1 A, 2 A, 3.5 A settable |
Recharge time | Standard model: 90% capacity restored in 4 hours; Long time model: depend on the capacity of battery |
SYSTEM | |
Efficiency | ≥ 93%, ECO mode 98% |
Transfer time | 0 ms |
Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure |
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP (optional) |
Max. number of parallel connections | 6 |
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional) |
Display | LCD + LED |
Standards | EN 62040-1, EN 62040-2, EN 61000-3-12, EN 61000-3-2, EN 61000-3-11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2 |
OTHERS | |
Operating temperature | 0℃ ~ 40℃ |
Storage temperature | -25℃ ~ 55℃ (without batteries) |
Relative Humidity | 0 ~ 95% (non-condensing) |
Altitude | ≤ 1000 m, derating 1% for each additional 100 m |
IP rating | IP 20 |
Noise level at 1m | ≤ 65 dB |
Online thermal dissipation | 5773 BTU/hr |
Dimensions (W×D×H) (mm) | 350 × 655 × 732 (H) |
Net weight (kg) | 155 (S) |
Gross weight (kg) | 170(S) |